Design of gas fire extinguishing systems. Design of automatic gas fire extinguishing Design of gas fire extinguishing

The design of gas fire extinguishing installations (GSP) is carried out on the basis of a specialist's study of many parameters of the building, including quite specific aspects:

  • dimensions and design features of the premises;
  • number of premises;
  • distribution of premises by fire hazard categories (according to NPB No. 105-85);
  • the presence of people;
  • parameters of technological equipment;
  • characteristics of HVAC systems (heating, ventilation, air conditioning), etc.

In addition, the fire extinguishing project must take into account the requirements of the relevant rules and regulations - so the extinguishing system will be as effective as possible in fighting fires and safe for people in the building.

Thus, the choice of the designer of the gas fire extinguishing installation should be taken responsibly, it is better if the same contractor is responsible not only for the design of the facility, but also for the installation and further maintenance of the system.

Technical description of the object

A gas fire extinguishing installation is a complex system that is used to extinguish fires of classes A, B, C, E in enclosed spaces. The selection of the optimal GFFS (gas extinguishing agent) option for the UGP makes it possible not to be limited only to those rooms where there are no people, but also to actively use gas fire extinguishing to protect facilities where service personnel may be.

Technically, the installation is a complex of devices and mechanisms. As part of a gas fire extinguishing system:

  • modules or cylinders that serve to store and supply GFFS;
  • distributors;
  • pipelines;
  • nozzles (valves) with a locking and starting device;
  • manometers;
  • fire detectors that generate a fire signal;
  • control devices for UGP control;
  • hoses, adapters and other accessories.

The number of nozzles, the diameter and length of pipelines, as well as other parameters of the UGP, are calculated by the master-designer according to the methods of the Norms and Rules for the design of gas fire extinguishing installations (NPB No. 22-96).

Drawing up project documentation

The drafting of project documentation by the contractor is carried out in stages:

  1. Inspection of the building, clarification of customer requirements.
  2. Analysis of initial data, performing calculations.
  3. Drawing up a working version of the project, approving documentation with the customer.
  4. Registration of the final version of the project documentation, which includes:
    • text part;
    • graphic materials - the layout of the protected premises, the available technological equipment, the location of the UGP, the connection diagram, the cable routing;
    • specification of materials, equipment;
    • detailed estimate for installation;
    • work sheets.

The speed of installation of all equipment, as well as reliable and efficient operation of the system, depends on how competently and fully the UGP project is in the future.

Gas extinguishing module

For storage, protection from external influences and release of GFFS to eliminate the fire, special modules of gas fire extinguishing are used. Outwardly, these are metal cylinders equipped with a locking and starting device (ZPU) and a siphon tube. Those models in which liquefied gas is stored, in addition, have a device for controlling the mass of the GFFS (it can be either external or built-in).

The cylinders usually have an information plate, which is filled in by the person in charge or the UGP maintenance master. The following data must be entered on the plate regularly - the capacity of the module, the working pressure. Also, the modules should be marked:

  • from the manufacturer - trademark, serial number, compliance with GOST, expiration date, etc .;
  • working and test pressure;
  • the mass of an empty and charged cylinder;
  • capacity;
  • dates of tests, charges;
  • name of GOTV, its weight.

The activation of the module in case of fire occurs after the receipt of a signal from the manual start devices or the control and monitoring security and fire device to the starting device (CP). After triggering the PU, propellant gases are formed, creating excess pressure. Thanks to this, the ZPU is opened and the fire extinguishing gas comes out of the cylinder.

The cost of installing gas fire extinguishing

The UGP designer must carry out a preliminary calculation of the installation cost.

The price will depend on several factors:

  • the cost of technological equipment - modules, including components and the required number of GEF, control and monitoring devices, detectors, displays, cabling;
  • the height and area of ​​the protected premises (or premises);
  • the purpose of the object;
  • type GOTV.

Fire extinguishing system installation contract

A high-quality design of a gas fire extinguishing installation, calculation of installation, further maintenance of the system - we carry out all this for our customers.

Details such as:

  • cost of work,
  • payment order,
  • installation time frame,
  • our obligations towards the customer -

after discussion and approval with the client, they will be spelled out in the contract.

As a result, we get a job, and our client - a gas fire extinguishing system with a guaranteed high degree of reliability and quality.

Gas fire extinguishing is the most effective and, in many cases, the only way to automatically extinguish a fire (ignition). Gas extinguishing agents have been used in fire extinguishing systems for many years - they began to be widely used in Europe back in the 1950s. Gas has many advantages - it is most often an environmentally friendly substance that effectively extinguishes fires and does not harm property and interiors.

Modern gas fire extinguishing systems are truly unique. If a few years ago we knew only about a few varieties, then today new generations of gaseous extinguishing agents used in automatic fire extinguishing systems make it possible to speak of themselves as absolutely safe, environmentally friendly products that quickly evaporate from the atmosphere.

The area of ​​application of gas fire extinguishing systems is wide - they are used wherever the use of water, powder or foam is undesirable or impossible - at facilities where there is a lot of electronic computing equipment (server, computer centers, hardware), where even a short-term power outage can lead to extremely serious consequences (for example, on airplanes and on ships), as well as in premises where securities or works of art are stored - archives, libraries, museums, art galleries.

Gas fire extinguishing design cost

List of design works


Choosing a specialist

The use of the latest gas fire extinguishing systems requires a number of preparatory and design work, on which the flawless operation of the entire automatic fire extinguishing system as a whole largely depends.


The design of gas fire extinguishing should be carried out by specialists, since all calculations are made in accordance with the rules established by law. The design of gas fire extinguishing systems is based on the analysis of several parameters: the number of rooms, their size, as well as the presence of suspended ceilings and partitions, the area of ​​doorways, the temperature regime at the facility, the air humidity in the room, the presence and mode of work of personnel are taken into account.

Based on these data, the required number of modules / tanks with gas is calculated, the diameter of the pipelines through which the gas will be supplied to the fire site, as well as the number and size of holes in the nozzles that spray the gas.


Equipment selection

The advanced technologies and improved developments of the 3M company have made it possible to create an absolutely safe, environmentally friendly product of a new generation - the gas substance Novec 1230. The composition contains non-corrosive components with excellent dielectric properties.


The gaseous substance is not absorbed into surfaces that are sensitive to moisture, it evaporates quickly, as a result of which there is no damage to valuable property, for example, when extinguishing a fire, archival materials, electrical equipment, computers, as well as objects of art are not damaged by the Novec 1230 gas substance used for fire extinguishing.

A mandatory requirement of the current standards is the calculation of the need to organize openings to relieve excess pressure, the integration of the AUGPT into the building, the organization of gas exhaust from the protected premises after extinguishing a fire. All these complex calculations are performed according to approved methods and require special engineering knowledge.

MINISTRY OF THE INTERIOR
RUSSIAN FEDERATION

STATE FIRE SERVICE

FIRE SAFETY STANDARDS

GAS FIRE EXTINGUISHING UNITS AUTOMATIC

STANDARDS AND RULES FOR DESIGN AND APPLICATION

NPB 22-96

MOSCOW 1997

Developed by the All-Russian Research Institute of Fire Protection (VNIIPO) of the Ministry of Internal Affairs of Russia. Submitted and prepared for approval by the regulatory and technical department of the Main Directorate of the State Fire Service (GUGPS) of the Ministry of Internal Affairs of Russia. Approved by the chief state inspector of the Russian Federation for fire supervision. Agreed with the Ministry of Construction of Russia (letter No. 13-691 of 19.12.1996). They were put into effect by order of the GUGPS of the Ministry of Internal Affairs of Russia dated December 31, 1996, No. 62. Instead of SNiP 2.04.09-84 in the part related to automatic gas fire extinguishing installations (section 3). Effective date 01.03.1997

Norms of the State Fire Service of the Ministry of Internal Affairs of Russia

GAS FIRE EXTINGUISHING UNITS AUTOMATIC.

Norms and rules for design and application

AUTOMATIC GAS FIRE EXTINGUISHING INSTALLATIONS.

Standards and rules of desing and used

Date of introduction 03/01/1997

1 AREA OF USE

These Standards apply to the design and use of automatic gas fire extinguishing installations (hereinafter referred to as AUGP). These Standards do not define the scope and do not apply to AUGP for buildings and structures designed according to special vehicle regulations. The use of AUGP, depending on the functional purpose of buildings and structures, the degree of fire resistance, the category of fire and explosion hazard and other indicators, is determined by the relevant current regulatory and technical documents approved in the prescribed manner. When designing, in addition to these standards, the requirements of other federal regulatory documents in the field of fire safety must be met.

2. REGULATORY REFERENCES

In these Standards, references to the following documents are used: GOST 12.3.046-91 Automatic fire extinguishing installations. General technical requirements. GOST 12.2.047-86 Fire fighting equipment. Terms and Definitions. GOST 12.1.033-81 Fire safety. Terms and Definitions. GOST 12.4.009-83 Fire fighting equipment for the protection of facilities. The main types. Accommodation and service. GOST 27331-87 Fire fighting equipment. Fire classification. GOST 27990-88 Means of security, fire and security and fire alarm systems. General technical requirements. GOST 14202-69 Industrial pipelines. Identification colors, warning signs and marking plates. GOST 15150-94 Machines, devices and other technical products. Versions for different climatic regions. Categories, conditions of climatic factors of the external environment. GOST 28130 Fire fighting equipment. Fire extinguishers, fire extinguishing and fire alarm systems. Graphic designations. GOST 9.032-74 Paint and varnish coatings. Groups, technical requirements and designations. GOST 12.1.004-90 Organization of occupational safety training. General Provisions. GOST 12.1.005-88 General sanitary and hygienic requirements for the air in the working area. GOST 12.1.019-79 Electrical safety. General requirements and nomenclature of types of protection. GOST 12.2.003-91 SSBT. Manufacturing equipment. General safety requirements. GOST 12.4.026-76 Signal colors and safety signs. SNiP 2.04.09.84 Fire automation of buildings and structures. SNiP 2.04.05.92 Heating, ventilation and air conditioning. SNiP 3.05.05.84 Process equipment and process pipelines. SNiP 11-01-95 Instructions on the procedure for the development, coordination, approval and composition of project documentation for the construction of enterprises, buildings and structures. SNiP 23.05-95 Natural and artificial lighting. NPB 105-95 Norms of the State Fire Service of the Ministry of Internal Affairs of Russia. Determination of categories of premises and buildings for explosion and fire safety. NPB 51-96 Gas fire-extinguishing compounds. General technical requirements for fire safety and test methods. NPB 54-96 Automatic gas fire extinguishing installations. Modules and batteries. General technical requirements. Test methods. PUE-85 Electrical Installation Rules. - M .: ENERGOATOMIZDAT, 1985 .-- 640 p.

3. DEFINITIONS

In these Standards, the following terms are used with the corresponding definitions and abbreviations.

Definition

The document on the basis of which the definition is given

Automatic installation of gas fire extinguishing (AUGP) A set of stationary technical fire extinguishing means for extinguishing fires through the automatic release of a gas extinguishing agent
NPB 51-96
Centralized automatic gas fire extinguishing system AUGP containing batteries (modules) with a fire fighting station, located in a fire extinguishing station, and designed to protect two or more rooms
Modular automatic gas fire extinguishing system AUGP containing one or more modules with UES, located directly in the protected room or next to it
Gas extinguishing battery NPB 54-96
Gas extinguishing module NPB 54-96
Gas fire extinguishing composition (GOS) NPB 51-96
Nozzles Device for the release and distribution of GOS in the protected room
Inertia of AUGP Time from the moment the signal is generated to start the AUGP to the beginning of the expiration of the GOS from the nozzle to the protected room without taking into account the delay time
Duration (time) of GOS supply t under, s Time from the beginning of the expiration of the GOS from the nozzle until the moment of release from the installation of the estimated mass of the GOS required to extinguish a fire in the protected room
Normative volumetric fire extinguishing concentration Cn,% vol. The product of the minimum volumetric fire extinguishing concentration of GOS by the safety factor equal to 1.2
Standard mass fire extinguishing concentration q N, kg × m -3 The product of the standard volumetric concentration of GOS by the density of GOS in the gas phase at a temperature of 20 ° C and a pressure of 0.1 MPa
Room leakage parameter d = S F H / V P, m -1 The value characterizing the leakage of the protected premises and representing the ratio of the total area of ​​permanently open openings to the volume of the protected premises
Leakage rate,% The ratio of the area of ​​permanently open openings to the area of ​​enclosing structures
Maximum overpressure in the room P m, MPa The maximum value of pressure in the protected room when the calculated amount of waste water is discharged into it
GOS reserve GOST 12.3.046-91
GOS stock GOST 12.3.046-91
Maximum jet size GOS Distance from the nozzle to the section, where the velocity of the gas-air mixture is not less than 1.0 m / s
Local, start (turn on) NPB 54-96

4. GENERAL REQUIREMENTS

4.1. The equipment of buildings, structures and premises of the AUGP must be carried out in accordance with the design documentation developed and approved in accordance with SNiP 11-01-95. 4.2. AUGP based on gas fire extinguishing compositions are used to eliminate fires of classes A, B, C in accordance with GOST 27331 and electrical equipment (electrical installations with a voltage not higher than those specified in the TD for the used GOS), with a leakage parameter of no more than 0.07 m -1 and a degree of leakage not more than 2.5%. 4.3. AUGP based on GOS should not be used to extinguish fires: - fibrous, loose, porous and other combustible materials prone to spontaneous combustion and (or) smoldering inside the volume of the substance (sawdust, cotton, grass flour, etc.); - chemicals and their mixtures, polymeric materials prone to smoldering and burning without air access; - metal hydrides and pyrophoric substances; - metal powders (sodium, potassium, magnesium, titanium, etc.).

5. DESIGNING AUGP

5.1. GENERAL PROVISIONS AND REQUIREMENTS

5.1.1. The design, installation and operation of the AUGP should be carried out in accordance with the requirements of these Standards, other applicable regulatory documents in terms of gas fire extinguishing installations, and taking into account the technical documentation for the AUGP elements. 5.1.2. AUGP includes: - modules (batteries) for storage and supply of gas extinguishing composition; - switchgears; - main and distribution pipelines with the necessary fittings; - nozzles for the release and distribution of GOS in the protected volume; - fire detectors, technological sensors, electrical contact pressure gauges, etc.; - devices and devices for monitoring and control of AUGP; - devices that form command impulses for shutdown of ventilation, air conditioning, air heating systems and technological equipment in the protected room; - devices that generate and issue command impulses for closing fire dampers, ventilation duct dampers, etc .; - devices for signaling about the position of doors in the protected area; - devices for sound and light signaling and notification of the unit activation and gas start-up; - fire alarm loops, electrical supply circuits, control and monitoring of AUGP. 5.1.3. The design of the equipment included in the AUGP is determined by the project and must comply with the requirements of GOST 12.3.046, NPB 54-96, PUE-85 and other applicable regulatory documents. 5.1.4. The initial data for the calculation and design of AUGP are: - the geometric dimensions of the room (length, width and height of the enclosing structures); - construction of floors and the location of utilities; - the area of ​​permanently open openings in the enclosing structures; - the maximum permissible pressure in the protected room (based on the strength of building structures or equipment located in the room); - the range of temperature, pressure and humidity in the protected room and in the room in which the AUGP components are located; - a list and indicators of the fire hazard of substances and materials in the room, and the corresponding fire class in accordance with GOST 27331; - type, size and distribution of the brew load; - normative volumetric fire extinguishing concentration of GOS; - availability and characteristics of ventilation systems, air conditioning, air heating; - characteristics and arrangement of technological equipment; - category of premises according to NPB 105-95 and classes of zones according to PUE-85; - the presence of people and their evacuation routes. 5.1.5. Calculation of AUGP includes: - determination of the estimated mass of the GOS required for extinguishing a fire; - determination of the duration of the GOS supply; - determination of the diameter of the pipelines of the installation, the type and number of nozzles; - determination of the maximum overpressure when supplying GOS; - determination of the required reserve of GOS and batteries (modules) for centralized installations or a stock of GOS and modules for modular installations; - determination of the type and required number of fire detectors or sprinklers of the incentive system. The procedure for calculating the diameter of pipelines and the number of nozzles for a low-pressure installation with carbon dioxide is given in the recommended Appendix 4. For a high-pressure installation with carbon dioxide and other gases, the calculation is carried out according to the methods agreed in the prescribed manner. 5.1.6. AUGP must ensure that the supply to the protected premises is not less than the estimated mass of the GOS, intended for extinguishing a fire, for the time specified in clause 2 of mandatory Appendix 1. 5.1.7. AUGP should provide a delay in the release of the UGS for the time necessary for the evacuation of people after the light and sound notification, stopping the ventilation equipment, closing the air dampers, fire dampers, etc., but not less than 10 s. The required evacuation time is determined in accordance with GOST 12.1.004. If the required evacuation time does not exceed 30 s, and the time for stopping ventilation equipment, closing air dampers, fire dampers, etc. Exceeds 30 s, then the mass of the UGS must be calculated based on the condition of ventilation and (or) leakage available at the time of release of the UGS. 5.1.8. The equipment and the length of the pipelines must be selected on the condition that the inertia of the AUGP operation should not exceed 15 s. 5.1.9. The AUGP distribution pipeline system, as a rule, must be symmetrical. 5.1.10. AUGP pipelines in fire hazardous areas should be made of metal pipes. It is allowed to use high-pressure hoses to connect modules to a manifold or main pipeline. The conditional passage of incentive pipelines with sprinklers should be taken equal to 15 mm. 5.1.11. The connection of pipelines in fire extinguishing installations should, as a rule, be performed by welding or threaded connections. 5.1.12. Pipelines and their connections in AUGP must ensure strength at a pressure equal to 1.25 R RAB, and tightness at a pressure equal to R RAB. 5.1.13. According to the method of storing the gas fire-extinguishing composition, AUGP are divided into centralized and modular. 5.1.14. AUGP equipment with centralized storage of GOS should be placed in fire extinguishing stations. The premises of fire extinguishing stations should be separated from other premises by type 1 fire partitions and type 3 ceilings. Fire extinguishing station premises, as a rule, should be located in the basement or on the ground floor of buildings. It is allowed to place a fire extinguishing station above the first floor, while the lifting and transporting devices of buildings, structures must ensure the possibility of delivering equipment to the installation site and carrying out maintenance work. The exit from the station should be provided to the outside, to the staircase, which has an exit to the outside, to the lobby or to the corridor, provided that the distance from the exit from the station to the staircase does not exceed 25 m and there are no exits to rooms of categories A, B and B, with the exception of rooms equipped with automatic fire extinguishing installations. An isothermal tank for storing the waste water treatment plant is allowed to be installed outside the premises with a canopy for protection from precipitation and solar radiation with a mesh fence around the perimeter of the site. 5.1.15. The premises of fire extinguishing stations must be at least 2.5 m high for installations with cylinders. The minimum height of the room when using an isothermal container is determined by the height of the container itself, taking into account the provision of a distance from it to the ceiling of at least 1 m.The rooms should have a temperature of 5 to 35 ° C, relative humidity of no more than 80% at 25 ° C, illumination - not less than 100 lux with fluorescent lamps or not less than 75 lux with incandescent lamps. Emergency lighting must comply with the requirements of SNiP 23.05.07-85. The premises of the stations should be equipped with supply and exhaust ventilation with at least double air exchange within 1 hour. The stations should be equipped with telephone communication with the premises of the duty personnel, who are on duty around the clock. At the entrance to the station premises, a light board "Fire extinguishing station" should be installed. 5.1.16. The equipment of modular gas fire extinguishing installations can be located both in the protected sanitary room and outside, in the immediate vicinity of it. 5.1.17. The placement of devices for local starting of modules, batteries and switchgears should be at a height of no more than 1.7 m from the floor. 5.1.18. The location of the equipment of centralized and modular AUGP should ensure the possibility of its maintenance. 5.1.19. The choice of the type of nozzles is determined by their performance characteristics for a specific GOS specified in the technical documentation for the nozzles. 5.1.20. The nozzles should be placed in the protected room in such a way as to ensure the concentration of GOS throughout the entire volume of the room not lower than the standard. 5.1.21. The difference in flow rates between the two extreme nozzles on the same distribution pipeline should not exceed 20%. 5.1.22. The AUGP should provide for devices that exclude the possibility of clogging of the nozzles during the release of the GOS. 5.1.23. Only one type of nozzle should be used in one room. 5.1.24. When the attachments are located in places of their possible mechanical damage, they must be protected. 5.1.25. The painting of the components of installations, including pipelines, must comply with GOST 12.4.026 and industry standards. Installation piping and modules located in rooms with special aesthetic requirements can be painted in accordance with these requirements. 5.1.26. All external surfaces of pipelines should be painted with protective paint in accordance with GOST 9.032 and GOST 14202. 5.1.27. Equipment, products and materials used in AUGP must have documents certifying their quality and comply with the conditions of use and project specifications. 5.1.28. AUGP of a centralized type, in addition to the calculated one, must have a 100% reserve of gas extinguishing composition. Batteries (modules) for storing the main and reserve GOS must have cylinders of the same standard size and be filled with the same amount of gas extinguishing agent. 5.1.29. AUGP of modular type, having gas fire extinguishing modules of the same standard size at the facility, must have a stock of GOS at the rate of 100% replacement in the installation that protects the largest room. If at one facility there are several modular installations with modules of different standard sizes, then the stock of GOS should ensure the restoration of the operability of installations that protect the premises of the largest volume with modules of each standard size. The stock of GOS must be kept in the warehouse of the facility. 5.1.30. If it is necessary to test AUGP, the stock of GOS for carrying out these tests is taken from the condition of protecting the premises of the smallest volume, if there are no other requirements. 5.1.31. The equipment used for AUGP must have a service life of at least 10 years.

5.2. GENERAL REQUIREMENTS FOR ELECTRIC CONTROL, CONTROL, SIGNALING AND POWER SUPPLY SYSTEMS AUGP

5.2.1. Electrical controls of the AUGP must provide: - automatic start-up of the installation; - shutdown and restoration of the automatic start mode; - automatic switching of power supply from the main source to the reserve one when the voltage is turned off at the main source, followed by switching to the main power source when the voltage is restored on it; - remote start of the installation; - turning off the sound alarm; - delay in the release of UGS for the time required to evacuate people from the premises, turn off ventilation, etc., but not less than 10 s; - formation of a command impulse at the outputs of electrical equipment for use in control systems for technological and electrical equipment of the facility, fire warning systems, smoke removal, air pressurization, as well as for switching off ventilation, air conditioning, air heating; - automatic or manual shutdown of sound and light alarms about fire, operation and malfunction of the installation. Notes: 1. Local start-up should be excluded or blocked in modular installations in which gas fire extinguishing modules are located inside the protected room. 2. For centralized installations and modular installations with modules located outside the protected area, the modules (batteries) must have a local start. 3. In the presence of a closed system serving only this room, it is allowed not to turn off ventilation, air conditioning, air heating after the supply of UGS to it. 5.2.2. Formation of a command pulse for automatic start-up of a gas fire extinguishing installation must be carried out from two automatic fire detectors in one or different loops, from two electrical contact pressure gauges, two pressure alarms, two process sensors or other devices. 5.2.3. Remote start devices should be placed at emergency exits outside the protected room or room, which includes the protected channel, underground, space behind the suspended ceiling. It is allowed to place remote start devices in the premises of the personnel on duty with mandatory indication of the AUGP operating mode. 5.2.4. Remote start devices for installations must be protected in accordance with GOST 12.4.009. 5.2.5. AUGP protecting rooms in which people are present must have automatic start-up disconnection devices in accordance with the requirements of GOST 12.4.009. 5.2.6. When opening the doors to the protected room, the AUGP must provide blocking of the automatic start-up of the installation with indication of the blocked state according to p. 5.2.15. 5.2.7. Devices for restoring the automatic start-up mode of the AUGP should be placed in the premises of the duty personnel. If there is protection against unauthorized access to the devices for restoring the automatic start mode of the AUGP, these devices can be placed at the entrances to the protected premises. 5.2.8. The AUGP equipment should provide automatic control of: - the integrity of the fire alarm loops along their entire length; - the integrity of the electrical starting circuits (open circuit); - air pressure in the incentive network, starting cylinders; - light and sound signaling (automatically or on call). 5.2.9. In the presence of several directions of GOS supply, the batteries (modules) and switchgears installed in the fire extinguishing station must have plates indicating the protected room (direction). 5.2.10. In the rooms protected by volumetric gas fire extinguishing installations, and in front of the entrances to them, an alarm should be provided in accordance with GOST 12.4.009. Similar alarms should be installed in adjacent rooms that have an exit only through the protected rooms, as well as rooms with protected channels, undergrounds and spaces behind the suspended ceiling. In this case, the light board "Gas - go away!", "Gas - do not enter" and the warning sound alarm device are installed common for the protected room and protected spaces (channels, underground, behind the suspended ceiling) of this room, and when protecting only these spaces - common for these spaces. 5.2.11. Before entering the protected room or the room to which the protected channel or underground belongs, the space behind the suspended ceiling, it is necessary to provide light indication of the AUGP operating mode. 5.2.12. In the premises of gas fire extinguishing stations, there should be a light signaling that fixes: - the presence of voltage at the inputs of the working and backup power sources; - breakage of electric circuits of squibs or electromagnets; - pressure drop in the stimulating pipelines by 0.05 MPa and starting cylinders by 0.2 MPa with decoding in directions; - AUGP triggering with decoding in directions. 5.2.13. In the premises of the fire post or in another room with personnel on duty around the clock, light and sound alarms should be provided: - on the occurrence of a fire with decoding in directions; - on the operation of the AUGP, with decoding according to the directions and the receipt of the UES in the protected premises; - about the disappearance of the voltage of the main power supply; - about AUGP malfunction with decoding in directions. 5.2.14. In AUGP, the sound signals about fire and operation of the installation must differ in tone from the signals about a malfunction. 5.2.15. In the room with the personnel on duty around the clock, only light signaling should also be provided: - about the AUGP mode of operation; - about turning off the sound alarm about fire; - about turning off the sound signaling about a malfunction; - on the presence of voltage on the main and backup power supplies. 5.2.16. AUGP must relate to consumers of electricity of the 1st category of power supply reliability according to PUE-85. 5.2.17. In the absence of a backup input, it is allowed to use autonomous power supplies that ensure the operability of the AUGP for at least 24 hours in standby mode and for at least 30 minutes in fire or malfunction mode. 5.2.18. The protection of electrical circuits must be carried out in accordance with PUE-85. The device of thermal and maximum protection in the control circuits is not allowed, the disconnection of which can lead to a failure to supply UGS to the protected room. 5.2.19. Grounding and grounding of the AUGP equipment must be carried out in accordance with PUE-85 and the requirements of the technical documentation for the equipment. 5.2.20. The selection of wires and cables, as well as the methods of their laying, should be carried out in accordance with the requirements of PUE-85, SNiP 3.05.06-85, SNiP 2.04.09-84 and according to the technical characteristics of cable and wire products. 5.2.21. The placement of fire detectors inside the protected premises should be carried out in accordance with the requirements of SNiP 2.04.09-84 or another regulatory document that replaces it. 5.2.22. The premises of the fire station or other premises with personnel on duty around the clock must comply with the requirements of section 4 of SNiP 2.04.09-84.

5.3. REQUIREMENTS FOR PROTECTED AREAS

5.3.1. Premises equipped with AUGP must be equipped with signs in accordance with paragraphs. 5.2.11 and 5.2.12. 5.3.2. The volumes, areas, combustible load, the presence and dimensions of open openings in the protected premises must correspond to the design and upon commissioning of the AUGP must be monitored. 5.3.3. Leakage of premises equipped with AUGP should not exceed the values ​​specified in clause 4.2. Measures should be taken to eliminate technologically unjustified openings, door closers, etc. should be installed. Premises, if necessary, should have pressure relief devices. 5.3.4. In the systems of air ducts for general ventilation, air heating and air conditioning of the protected premises, air locks or fire dampers should be provided. 5.3.5. To remove the waste water treatment plant after the end of the AUGP operation, it is necessary to use general ventilation of buildings, structures and premises. It is allowed for this purpose to provide mobile ventilation units.

5.4. SAFETY AND ENVIRONMENTAL REQUIREMENTS

5.4.1. The design, installation, commissioning, acceptance and operation of the AUGP should be carried out in accordance with the requirements of the safety measures set forth in: - "Rules for the Design and Safe Operation of Pressure Vessels"; - "Rules for the technical operation of electrical installations of consumers"; - "Safety regulations for the operation of electrical installations by consumers of the State Energy Supervision Service"; - "Uniform safety rules for blasting operations (when using pyro-cartridges in installations"); - GOST 12.1.019, GOST 12.3.046, GOST 12.2.003, GOST 12.2. 005, GOST 12.4.009, GOST 12.1.005, GOST 27990, GOST 28130, PUE-85, NPB 51-96, NPB 54-96; - these Standards; - the current normative and technical documentation, approved in accordance with the established procedure in terms of AUGP. 5.4.2. Devices for local start-up of installations must be fenced and sealed, with the exception of local start-up devices installed in the premises of a fire extinguishing station or fire posts. 5.4.3. It is allowed to enter the protected area after the release of the GOS and extinguish the fire until the end of ventilation only in insulating respiratory protection. 5.4.4. Entering the room without insulating respiratory protection is allowed only after removing the combustion products and decomposition of GOS to a safe value.

ANNEX 1
Mandatory

Methodology for calculating the parameters of AUGP for extinguishing by volumetric method

1. The mass of the gas extinguishing composition (Mg), which must be stored in the AUGP, is determined by the formula

M G = Mr + Mtr + M 6 × n, (1)

Where Мр is the estimated mass of the GOS, intended for extinguishing a fire in a volumetric way in the absence of artificial ventilation of air in the room, is determined: for ozone-safe freons and sulfur hexafluoride according to the formula

Мр = К 1 × V P × r 1 × (1 + К 2) × С Н / (100 - С Н) (2)

For carbon dioxide according to the formula

Мр = К 1 × V P × r 1 × (1 + К 2) × ln [100 / (100 - С Н)], (3)

Where V P is the estimated volume of the protected premises, m 3. The calculated volume of the room includes its internal geometric volume, including the volume of a closed ventilation, air conditioning, and air heating system. The volume of equipment in the room is not deducted from it, with the exception of the volume of solid (impenetrable) building fireproof elements (columns, beams, foundations, etc.); K 1 is a coefficient that takes into account the leaks of a gas extinguishing agent from cylinders through leaks in the valves; K 2 is a coefficient that takes into account the loss of a gas extinguishing composition through leaks in the room; r 1 is the density of the gas extinguishing composition, taking into account the height of the protected object relative to sea level, kg × m -3, is determined by the formula

r 1 = r 0 × T 0 / T m × K 3, (4)

Where r 0 is the vapor density of the gas extinguishing composition at a temperature of T o = 293 K (20 ° C) and an atmospheric pressure of 0.1013 MPa; Tm is the minimum operating temperature in the protected room, K; С Н - standard volumetric concentration of GOS,% vol. The values ​​of the standard fire extinguishing concentrations of GOS (C H) for various types of combustible materials are given in Appendix 2; K z - a correction factor that takes into account the height of the object relative to sea level (see Table 2 of Appendix 4). The remainder of the waste water treatment plant in pipelines М МР, kg, is determined for AUGP, in which the nozzle holes are located above the distribution pipelines.

M tr = V tr × r GOS, (5)

Where V tr is the volume of AUGP pipelines from the nozzle closest to the installation to the end nozzles, m 3; r GOS - the density of the residual GOS at the pressure that exists in the pipeline after the end of the outflow of the estimated mass of the gaseous fire-extinguishing composition into the protected room; M b × n is the product of the remainder of the GOS in the battery (module) (M b) of the AUGP, which is accepted according to the TD for the product, kg, by the number (n) of batteries (modules) in the installation. In rooms in which, during normal operation, significant fluctuations in volume (warehouses, storage facilities, garages, etc.) or temperature are possible, it is necessary to use the maximum possible volume as the calculated volume, taking into account the minimum operating temperature of the room. The standard volumetric fire extinguishing concentration С Н for combustible materials not listed in Appendix 2 is equal to the minimum volumetric fire extinguishing concentration multiplied by the safety factor of 1.2. The minimum volumetric fire extinguishing concentration is determined according to the method described in NPB 51-96. 1.1. The coefficients of equation (1) are determined as follows. 1.1.1. Coefficient that takes into account leaks of a gas extinguishing composition from vessels through leaks in the valves and uneven distribution of the gas extinguishing composition over the volume of the protected room:

1.1.2. Coefficient that takes into account the loss of a gas extinguishing agent through leaks in the room:

K 2 = 1.5 × F (Sn, g) × d × t POD ×, (6)

Where F (Cn, g) is a functional coefficient that depends on the standard volumetric concentration of C H and the ratio of the molecular masses of air and gas extinguishing composition; g = t W / t GOS, m 0.5 × s -1, is the ratio of the ratio of the molecular masses of air and GOS; d = S F H / V P - room leakage parameter, m -1; S F H - total area of ​​leakage, m 2; H is the height of the room, m. The coefficient F (Cn, g) is determined by the formula

F (Cn, y) = (7)

Where = 0.01 × C H / g is the relative mass concentration of GOS. The numerical values ​​of the coefficient Ф (Cn, g) are given in reference annex 5. 2. The time of release into the protected room of the calculated mass of the GOS, intended for extinguishing a fire, should not exceed a value equal to: t POD £ 10 s for modular AUGP, using as GOS freons and sulfur hexafluoride; t POD £ 15 s for centralized AUGP, using freons and sulfur hexafluoride as GOS; t POD £ 60 s for AUGP using carbon dioxide as GOS. 3. The mass of a gas extinguishing agent intended for extinguishing a fire in a room with a working forced ventilation: for freons and sulfur hexafluoride

Mg = K 1 × r 1 × (V p + Q × t POD) × [CH / (100 - CH)] (8)

For carbon dioxide

Mg = K 1 × r 1 × (Q × t POD + V p) × ln [100/100 - CH)] (9)

Where Q is the volumetric flow rate of air removed by ventilation from the room, m 3 × s -1. 4. Maximum overpressure when supplying gas compositions with leaks in the room:

< Мг /(t ПОД × j × ) (10)

Where j = 42 kg × m -2 × C -1 × (% vol.) -0.5 is determined by the formula:

Pt = [CH / (100 - CH)] × Pa or Pt = Pa + D RT, (11)

And with a leaky room:

³ Mg / (t POD × j ×) (12)

Determined by the formula

(13)

5. The release time of the WTP depends on the pressure in the cylinder, the type of the WTP, the geometric dimensions of the pipelines and nozzles. The release time is determined when carrying out hydraulic calculations of the installation and should not exceed the value specified in clause 2. of Appendix 1.

APPENDIX 2
Mandatory

Table 1

Normative volumetric fire extinguishing concentration of Freon 125 (C 2 F 5 H) at t = 20 ° C and P = 0.1 MPa

GOST, TU, OST

volume,% vol.

Mass, kg × m -3

Ethanol GOST 18300-72
N-heptane GOST 25823-83
Vacuum oil
Cotton fabric OST 84-73
PMMA
Organoplastic TOPS-Z
Textolite B GOST 2910-67
Rubber IRP-1118 TU 38-005924-73
Nylon fabric P-56P TU 17-04-9-78
OST 81-92-74

table 2

Standard volumetric fire extinguishing concentration of sulfur hexafluoride (SP 6) at t = 20 ° C and P = 0.1 MPa

The name of the combustible material

GOST, TU, OST

Standard fire extinguishing concentration SN

volume,% vol.

mass, kg × m -3

N-heptane
Acetone
Transformer oil
PMMA GOST 18300-72
Ethanol TU 38-005924-73
Rubber IRP-1118 OST 84-73
Cotton fabric GOST 2910-67
Textolite B OST 81-92-74
Cellulose (paper, wood)

Table 3

Standard volumetric fire extinguishing concentration of carbon dioxide (CO 2) at t = 20 ° C and P = 0.1 MPa

The name of the combustible material

GOST, TU, OST

Standard fire extinguishing concentration SN

volume,% vol.

Mass, kg × m -3

N-heptane
Ethanol GOST 18300-72
Acetone
Toluene
Kerosene
PMMA
Rubber IRP-1118 TU 38-005924-73
Cotton fabric OST 84-73
Textolite B GOST 2910-67
Cellulose (paper, wood) OST 81-92-74

Table 4

Standard volumetric fire extinguishing concentration of freon 318C (C 4 F 8 C) at t = 20 ° C and P = 0.1 MPa

The name of the combustible material

GOST, TU, OST

Standard fire extinguishing concentration SN

volume,% vol.

mass, kg × m -3

N-heptane GOST 25823-83
Ethanol
Acetone
Kerosene
Toluene
PMMA
Rubber IRP-1118
Cellulose (paper, wood)
Getinax
Expanded polystyrene

APPENDIX 3
Mandatory

General requirements for the installation of local fire extinguishing

1. Local volumetric fire extinguishing installations are used to extinguish the fire of individual units or equipment in cases where the use of volumetric fire extinguishing installations is technically impossible or economically inexpedient. 2. The estimated volume of local fire extinguishing is determined by the product of the base area of ​​the protected unit or equipment by their height. In this case, all design dimensions (length, width and height) of the unit or equipment must be increased by 1 m. 3. For local fire extinguishing by volume, carbon dioxide and freons should be used. 4. The standard fire extinguishing mass concentration for local extinguishing by volume with carbon dioxide is 6 kg / m 3. 5. The time for supplying the UGS with local extinguishing should not exceed 30 s.

Methodology for calculating the diameter of pipelines and the number of nozzles for a low-pressure installation with carbon dioxide

1. Average (for the time of supply) pressure in an isothermal vessel pt, MPa, is determined by the formula

p t = 0.5 × (p 1 + p 2), (1)

Where p 1 is the pressure in the container during storage of carbon dioxide, MPa; p 2 - pressure in the container at the end of the release of the calculated amount of carbon dioxide, MPa, is determined from Fig. 1.

Rice. 1. Graph for determining the pressure in an isothermal vessel at the end of the release of the calculated amount of carbon dioxide

2. Average consumption of carbon dioxide Q t, kg / s, is determined by the formula

Q t = t / t, (2)

Where m is the mass of the main stock of carbon dioxide, kg; t is the time of supply of carbon dioxide, s, taken according to clause 2 of Appendix 1. 3. The inner diameter of the main pipeline d i, m, is determined by the formula

d i = 9.6 × 10 -3 × (k 4 -2 × Q t × l 1) 0.19, (3)

Where k 4 is a factor, is determined from the table. 1; l 1 - the length of the main pipeline according to the project, m.

Table 1

4. Average pressure in the main pipeline at the point of its entry into the protected area

p s (p 4) = 2 + 0.568 × 1n, (4)

Where l 2 is the equivalent length of pipelines from the isothermal vessel to the point at which the pressure is determined, m:

l 2 = l 1 + 69 × d i 1.25 × e 1, (5)

Where e 1 is the sum of the resistance coefficients of the pipe fittings. 5. Medium pressure

p t = 0.5 × (p s + p 4), (6)

Where p z - pressure at the point of entry of the main pipeline into the protected room, MPa; p 4 - pressure at the end of the main pipeline, MPa. 6. Average flow rate through the nozzles Q t, kg / s, is determined by the formula

Q ¢ t = 4.1 × 10 -3 × m × k 5 × А 3 , (7)

Where m is the coefficient of flow through the nozzles; a 3 is the area of ​​the outlet of the nozzle, m; k 5 - coefficient determined by the formula

k 5 = 0.93 + 0.3 / (1.025 - 0.5 × p ¢ t). (eight)

7. The number of nozzles is determined by the formula

x 1 = Q т / Q ¢ т.

8. The inner diameter of the distribution pipeline (d ¢ i, m, is calculated from the condition

d ¢ I ³ 1,4 × d Ö x 1, (9)

Where d is the diameter of the nozzle outlet. The relative mass of carbon dioxide t 4 is determined by the formula t 4 = (t 5 - t) / t 5, where t 5 is the initial mass of carbon dioxide, kg.

APPENDIX 5
Reference

Table 1

Basic thermophysical and thermodynamic properties of freon 125 (C 2 F 5 H), sulfur hexafluoride (SF 6), carbon dioxide (CO 2) and freon 318C (C 4 F 8 C)

Name

unit of measurement

Molecular mass
Vapor density at P = 1 atm and t = 20 ° C
Boiling point at 0.1 MPa
Melting temperature
Critical temperature
Critical pressure
Density of liquid at P cr and t cr
Specific heat of liquid

kJ × kg -1 × ° С -1

kcal × kg -1 × ° С -1

Specific heat capacity of gas at P = 1 atm and t = 25 ° C

kJ × kg -1 × ° С -1

kcal × kg -1 × ° С -1

Latent heat of vaporization

kJ × kg

kcal × kg

Gas thermal conductivity coefficient

W × m -1 × ° С -1

kcal × m -1 × s -1 × ° С -1

Gas dynamic viscosity

kg × m -1 × s -1

Relative dielectric constant at P = 1 atm and t = 25 ° C

e × (e back) -1

Partial vapor pressure at t = 20 ° С
Breakdown voltage of GOS vapors relative to nitrogen gas

V × (V N2) -1

table 2

Correction factor taking into account the height of the protected object relative to sea level

Height, m

Correction factor K 3

Table 3

Values ​​of the functional coefficient F (Cn, g) for freon 318C (C 4 F 8 C)

Volume concentration of freon 318Ts SN,% vol.

Functional coefficient Ф (Cn, g)

Table 4

The value of the functional coefficient F (Cn, g) for freon 125 (C 2 F 5 N)

Volume concentration of freon 125 Cn,% vol.

Volume concentration of freon 125 Cn,% vol.

Functional coefficient (Cn, g)

Table 5

Values ​​of the functional coefficient Ф (Сn, g) for carbon dioxide (СО 2)

Functional coefficient (Cn, g)

Volumetric concentration of carbon dioxide (CO 2) Cn,% vol.

Functional coefficient (Cn, g)

Table 6

Values ​​of the functional coefficient Ф (Сn, g) for sulfur hexafluoride (SF 6)

Functional coefficient Ф (Cn, g)

The volumetric concentration of sulfur hexafluoride (SF 6) Cn,% vol.

Functional coefficient Ф (Cn, g)

1 area of ​​use. 1 2. Normative references. 1 3. Definitions. 2 4. General requirements. 3 5. Designing augp .. 3 5.1. General provisions and requirements. 3 5.2. General requirements for electrical control, control, signaling and power supply systems of augp .. 6 5.3. Requirements for protected premises .. 8 5.4. Safety and environmental requirements .. 8 Annex 1 Methodology for calculating the parameters of AUGP for extinguishing by volumetric method .. 9 Appendix 2 Standard volumetric fire extinguishing concentrations. eleven Appendix 3 General requirements for the installation of local fire extinguishing. 12 Appendix 4 Methodology for calculating the diameter of pipelines and the number of nozzles for a low-pressure installation with carbon dioxide. 12 Appendix 5 Basic thermophysical and thermodynamic properties of freon 125, sulfur hexafluoride, carbon dioxide and freon 318C .. 13

Designing fire extinguishing installations is not an easy task. It is sometimes not so easy to make a competent project and choose the right equipment, not only for novice designers, but also for engineers with experience. Many objects with their own characteristics and requirements (or their complete absence in regulatory documents). Seeing the need of our clients, TC TAKIR developed a separate program in 2014 and began to regularly conduct training on the design of fire extinguishing installations for specialists from different regions of Russia.

Training course "Design of fire extinguishing installations"

Why did many listeners choose TC TAKIR and our course on firefighting:

  • teachers are “not theoreticians”, but acting experts involved by the Companies in the design of fire protection equipment. Teachers know what problems specialists face in their work;
  • we do not have a task to sell you equipment of a specific manufacturer or convince you to include it in the project;
  • the lectures consider the requirements of the norms and the peculiarities of their application;
  • we are aware of the current changes in NTD and legislative acts;
  • in the classroom, hydraulic calculations are discussed in detail;
  • contacts received during training can be useful for students in their work. The answer to your question can be obtained faster by writing directly to the teacher by mail.

Fire extinguishing design training is carried out by:

Practical teachers with more than 10 years of experience in the design of fire extinguishing systems, representatives of VNIIPO and the Academy of State Fire Service of the Ministry of Emergencies of Russia, specialists from leading firms providing consulting services for the design of fire protection systems.

How to enroll in firefighting courses:

Courses are held once a quarter. Employees of the training center advise you to sign up for them in advance by filling out an application on the website or by phone. After reviewing your application, the staff will agree on a training date. Only after that you will be sent an invoice for payment and an agreement.

Upon completion of the firefighting course, a certificate of advanced training is issued.

Training on the course of designing fire extinguishing systems is carried out in the classrooms of the TAKIR training center in Moscow or onsite to the Customer's territory (for groups of 5 people or more).

Training in the design of fire extinguishing systems

Training program "Design of fire extinguishing installations" by day:

Day 1.

10.00-11.30 Construction of fire protection systems (SPZ)

  • Construction of fire detection systems. Operating principle.
  • Fire detection systems and control of fire extinguishing installations
  • Fire detectors. Reception and control devices. Control devices for fire extinguishing installations.

11.30-13.00 Fire extinguishing installations (FRU). Basic terms and definitions for fire extinguishing systems.

  • Basic terms and definitions. Classification of UFT according to purpose, type, type of extinguishing agent, response time, duration of action, nature of automation, etc.
  • The main design features of each type of DCS.

14.00-15.15 Design of fire extinguishing installations. Requirements for project documentation

  • Requirements for project documentation.
  • The procedure for the development of design documentation for UFT.
  • A brief algorithm for the selection of fire extinguishing installations in relation to the object of protection.

15.30-17.00 Introduction to the design of water-based fire extinguishing installations

  • Classification, main units and elements of sprinkler and deluge fire extinguishing installations.
  • General information on the construction of water and foam UPT and their technical means.
  • Diagrams of water fire extinguishing installations and operation algorithm.
  • The procedure for the development of a task for the design of DCT.

Day 2.

10.00-13.00 Hydraulic calculation of water fire extinguishing installations:

- determination of water consumption and the number of sprinklers,

- determination of the diameters of pipelines, pressure at nodal points, pressure losses in pipelines, control unit and shut-off valves, flow rate on subsequent sprinklers from the dictating sprinkler within the protected area, determination of the total design flow rate of the installation.

14.00-17.00 Design of foam fire extinguishing installations

  • Scope of foam fire extinguishing systems. System composition. Regulatory and technical requirements. Requirements for storage, use and disposal.
  • Devices for obtaining foam of various expansion rates.
  • Foaming agents. Classification, application features, regulatory requirements. Dosing system types.
  • Calculation of the amount of foaming agents for extinguishing low, medium and high expansion rates.
  • Features of the protection of tank farms.
  • The procedure for developing a task for the design of AUP.
  • Typical design solutions.

Day 3.

10.00-13.00 Application of powder fire extinguishing installations

The main stages of development of modern autonomous powder fire extinguishing means. Fire extinguishing powders and extinguishing principles. Powder fire extinguishing modules, types and features, areas of application. Operation of autonomous fire extinguishing installations based on powder modules.

The regulatory framework of the Russian Federation and the requirements for the design of powder fire extinguishing installations. Calculation methods for the design of modular fire extinguishing installations.

Modern methods of notification and control - types of fire and burglar alarms and control devices for automatic fire extinguishing systems. Wireless automatic fire extinguishing, alarm and warning system "Garant-R".

14.00-17.00 Management of fire extinguishing installations based on S2000-ASPT and Potok-3N

  • Functionality and design features.
  • Features of gas, powder and aerosol extinguishing based on S200-ASPT. Gas and powder modules, features of monitoring the state of the connected circuits.
  • Management of fire extinguishing installations based on the Potok-3N device: equipment of a pumping station for sprinkler, deluge, foam fire extinguishing, fire water supply at industrial and civil facilities.
  • Work with AWS "Orion-Pro".

Day 4.

10.00-13.00 Design of gas fire extinguishing installations (part 1).

Choice of gas extinguishing agent. Specific features of the use of specific OTS - Freon, Inergen, СО2, Novec 1230. Market overview of other gaseous fire extinguishing agents.

Development of a design assignment. Type and composition of the project assignment. Specific subtleties.

Calculation of the mass of the gaseous extinguishing agent. Calculation of the opening area for relieving excess pressure

14.00-17.00 Design of gas fire extinguishing installations (part 2). Practical lesson.

Development of an explanatory note. The main technical solutions and the concept of the future project. Selection and placement of equipment

Creation of working drawings. Where to start and what to look for. Piping design. Calculation of hydraulic flows. Optimization methods. Demonstration of performing calculations. Experience in using programs on real objects.

Drawing up a specification of equipment and materials. Development of assignments for related sections.

Day 5.

10.00-12.00 Design of water mist fire extinguishing installations (TRV).

  • Classification and principle of operation.
  • Application area.
  • Piping and fittings.
  • Features of the design of sprinkler fire extinguishing systems for expansion valves with forced start.
  • Typical design solutions.

12.00-15.00 Design of an internal fire-fighting water supply system (ERW).

Basic terms and definitions. ERW classification. Analysis of current international and domestic standards and regulations. The main design features of the ERW accessory equipment. The most important nomenclature and parameters of technical means of ERW. The main aspects of the choice of pumping units ERW. Features of the device ERW high-rise buildings. Brief algorithm for hydraulic calculation of ERW. Basic requirements for the design of ERW and the determination of the distance between fire hydrants. Basic requirements for the installation and operation of the ERW.

15.30-16.30 Installation and complex adjustment of AUP. NTD requirements for the installation of AUPT.

Responsible persons, organization of installation supervision. Registration of materials based on the results of installation. Features of acceptance into operation of AUPT. Documentation presented upon acceptance.

16.40-17.00
Final certification in the form of offset. Registration of accounting documents. Issuance of certificates.

Dates of study

Dates of study